HEMP Transformer Defense Through Power Electronics
High altitude electromagnetic pulses and geo-magnetic disturbances have the potential to severely impact the electric power grid by damaging large power transformers and causing severe power quality issues. This impact comes as a result of a quasi-static bias induced on transmission lines by geomagnetically induced currents which saturate magnetic components in the electric power system. This paper introduces the concept of utilizing a h-bridge inverter on the neutral of a LPT to inject a DC bias equivalent voltage onto the neutral side of the transformer windings. This biasing floats the transformer windings, eliminating the effect of the DC current and keeping the transformer from saturating. Schematic diagrams will be presented, along with simulation model data using Typhoon and PLECS, and finally test results from a benchtop hardware test.