Flexible Operation of Microgrids Through Operator-Configurable Microgrid Controllers

Microgrids are becoming critical assets in power distribution systems. This is partly due to the resiliency and reliability challenges faced by power distribution systems in the last decade and partly due to the increased integration of distributed energy resource assets, such as solar photovoltaic. This increased need for microgrids has created a multitude of needs for microgrid controllers. Most microgrid controllers in the past decade have been uniquely programmed or custom programmed to meet the needs of a specific microgrid. Currently, IEEE standards aim to integrate the needs and capabilities of microgrid controllers under a unified umbrella. But the standards do not recommend necessary or appropriate software development practices for microgrid controllers. In addition, the programmable nature and maintenance of controllers are also key characteristics that fall outside the coverage of the standards. In this paper, we present the best software practices that utility engineers and microgrid operators should consider in the microgrid software platform. This paper can be used as an information document for developing documentation of controller requirements and assessing microgrid controller requirements.

Banshee microgrid

Integrating a Microgrid Controller with a Local OpenADR Server

When military microgrids isolate themselves from the main electrical grid, they must locally balance electricity supply and demand. Since local generation may be limited, the current strategy is to shed all but the most critical loads by tripping smart circuit breakers, which must then be reset manually (e.g., ESTCP project EW-201350). This strategy is typically applied at the building level, meaning that entire buildings housing mission critical activities must be excluded from any load management, while those considered non-critical may lose service entirely. The remotely controlled switchgear needed to manage load in this way is very expensive ($\$30,000$-$\$50,000$ per building). While effective at shedding load, this strategy disrupts installation operation and risks damaging equipment during both disconnection and re-energization. With the goals of lowering costs, protecting equipment, and enhancing the agility of DoD microgrids, this report demonstrates the use of cybersecure automated demand response (ADR) technology to manage microgrid loads during grid-independent (a.k.a. "islanded") operation. This automated approach achieves load shedding and shifting through communication signals sent to equipment controllers rather than by cutting off the flow of electricity within the microgrid itself. Because it operates only on the base network, with no connection to external entities, this strategy avoids the main cybersecurity concern raised by past applications of ADR on military bases.

24 POWER TRANSMISSION AND DISTRIBUTION