Engineering Papers⌕ Search

Engineering topics

Bae, Yeonjin

Publications and source records attributed to Bae, Yeonjin.

34 records · Page 2

Implementation of ASHRAE Guideline 36 Control Logic into Oak Ridge National Laboratory (ORNL)’s Flexible Research Platform (FRP)

This report presents the initial field test procedure and results for ASHRAE Guideline 36 control logic. The US Department of Energy’s Oak Ridge National Laboratory’s (ORNL’s) two-story Flexible Research Platform (FRP-2) was selected as a test building. The rooftop unit (RTU) system serves as the building’s primary cooling system, and each variable air volume (VAV) box with an electric reheat coil serves as the building’s heating system along with RTU gas furnace. In this study, the control for the RTU and VAV box adopted the practical control sequences from ASHRAE Guideline 36-2018: High-Performance Sequences of Operation. Each story of the FRP-2 building has 5 office zones (thermal zones), for a total of 10 zones.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensor Impact Evaluation at Different Sensor Locations in a Multi-zone Office Building

FY 2022 Q1 deliverables include the development of an emulator that can evaluate the sensor impacts at different sensor locations (i.e., thermostat locations) in a multizone office building. This report presents the detailed procedure of developing the emulator and using the emulator for preliminary sensor impact analysis. In designing new multizone buildings or retrofitting existing buildings, the room thermostat locations or subzoning design has been often determined by best practices without considering the effects of this design in terms of energy or thermal comfort. In subzoning design, the total number of thermostats is usually smaller than the total number of rooms. As a result, one thermostat in one room often controls the indoor temperature of several other adjacent rooms. For example, five zones might share one thermostat located in one of the zones. Because the demands for thermal load in different zones could be different for the multizone buildings, this subzoning design can compromise control performance and waste building energy consumption. Furthermore, for multizone buildings, subzoning could introduce thermal discomfort for zones. This issue has not be thoroughly investigated in simulation/field studies, and the US Department of Energy’s Oak Ridge National Laboratory explored the impacts of subzoning design through modeling and experimental study.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Southeastern Focus Place-Based Technology Innovation Summit

This meeting focused on taking science-based action to realize decarbonized, place-based, clean energy interventions that are equally shaped by, inspired from, and committed to the communities they serve. We seek to make clean energy technologies applicable, relevant, and significant for all communities throughout the various scales of place—from Knoxville, Tennessee, to the Tennessee Valley Region, to the entire Southeast. This meeting matched researchers with community groups and businesses that are creating change in the built environment.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Connected Loads – Grid Connected Appliances: Commercial Refrigeration System Fault Detection and Diagnostics

As one of the most energy-intensive end-uses in the commercial buildings sector, supermarkets consume around 50 kWh/ft 2 (or 537.6 kWh/m 2 ) of electricity annually, or more than 2 million kWh of electricity per year for a typical store. The biggest consumer of energy in a supermarket is its refrigeration system, which accounts for 40–60% of its total electricity usage and is equivalent to about 2–3% of the total energy consumed by commercial buildings in United States, or around 0.5 quadrillion Btu (or 0.53 quadrillion KJ). Also, the supermarket refrigeration system is one of the biggest consumers of refrigerants. Current supermarket refrigeration systems rely on high global warming potential hydrofluorocarbon refrigerants. Reducing refrigerant usage or using environment friendly alternatives can result in significant climate benefits. Transcritical CO2 refrigeration systems have attracted more attention in recent years because of their zero-carbon emission advantages compared with traditional refrigerants. These systems are widely used in commercial buildings such as supermarkets. The refrigeration system can also be adapted to handle flexible building loads and be integrated into grid response transactive control to balance the supply and demand of the electric grid. Even minor improvements in the efficiency and operational reliability of supermarket refrigeration systems can create significant value in terms of saving energy, improving food quality, protecting the environment, reducing carbon footprint, and enhancing electric grid resilience.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensor impacts on building and HVAC controls: A critical review for building energy performance

Building operations rely heavily on control systems and sensors. This paper provides a sophisticated literature review on sensor systems in building/HVAC systems, particularly in the context of controls, and their impacts on energy efficiency and thermal comfort. This study aims to understand the previous and current research and identify future research opportunities on this subject. The reviewed sensor systems were used for heuristic rule-based controls, local controls, and advanced optimal controls for existing and emerging technologies. Five major aspects of sensors are reviewed here: control loops for sensors, sensor types, sensor locations, sensor data, and a sensor impact evaluation framework. To augment the literature review, comprehensive standardized interviews were also conducted with relevant industry experts and practitioners. These interviews were designed and performed to (1) identify significant factors for selecting sensor sets and current undergoing issues, (2) identify potential improvements in sensor configuration/deployment, and (3) integrate expert (e.g., researcher, building operation practitioner) knowledge and experiences to develop structured use-case scenarios. Researchers collected and analyzed 31 interview responses for this paper.

Building control↗

Sensor impact evaluation and verification for fault detection and diagnostics in building energy systems: A review

Sensors are the key information source for fault detection and diagnostics (FDD) in buildings. However, sensors are often not properly designed, installed, calibrated, located, and maintained, which negatively impacts FDD performance. Several sensor-related FDD topics have been widely studied, covering a wide range of fault types and applications. However, it is difficult to get a clear picture of the technical development of sensor-related topics in FDD. A systematic review of sensor topics is needed to summarize the existing research in a logical way, draw conclusions on the current development, and predict the future development of sensors in building FDD. To address this gap, we conducted a comprehensive literature review of more than 100 FDD-sensor-related papers. In this article, we subdivide the FDD tasks into building-level, system-level, and component-level FDD, and review sensor-related topics in each category. Our major conclusions are: (a) current data-driven FDD research focuses more on FDD algorithms than sensors, (b) sensor “hardware” research topics are less studied than sensor “software” topics, (c) very few papers focus on sensor engineering as an integral aspect of FDD development, and (d) some important sensor topics, such as sensor cost-effectiveness and sensor schema/layout/location, are not well studied. Finally, we discuss the need for a systematic framework of FDD sensors and models to integrate sensor design/selection, sensor data analysis/mining, feature selection, physics-based or data-driven algorithm development, sensor fault detection, sensor calibration, and sensor maintenance. Finally, expert interviews are conducted to validate the above findings and conclusions.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Surrogate Model of Flexible Research Platform EnergyPlus Models to Enable Sensitivity Analysis

This letter report describes the surrogate models developed from the EnergyPlus model of Oak Ridge National Laboratory’s Flexible Research Platform. Two data-driven black-box models were developed, and the outputs of the surrogate models were compared with the EnergyPlus model. The two models developed are a multilayer perceptron deep learning model, and a long short-term memory (LSTM) neural network model. The three factors for selecting the black-box models are scalability, computation time, and accuracy. A total of 107 input variables were the dominant variables in determining the outputs of building energy consumptions and thermal comfort. A total of 54 output variables were identified as the prediction targets, including the system- and zone-level outputs. The large set of the simulation cases were generated by integrating sensor errors into an emulator based on EnergyPlus and Python EMS, which includes advanced control sequences from ASHRAE Guideline 36-2018: High-Performance Sequences of Operation. The surrogate models were developed based on a set of large-scale simulation runs (i.e., 4,000 runs) on a cloud platform. The comparison analysis shows that the two black-box models had good accuracy for predicting new outputs for sensitivity analysis using the root mean square error metric. As a next step, the developed surrogate models will be used to perform sensitivity analysis for different sensor impacts (e.g., sensor types, sensor locations).

42 ENGINEERING↗

Dataset of low global warming potential refrigerant refrigeration system for fault detection and diagnostics

Abstract HVAC and refrigeration system fault detection and diagnostics (FDD) has attracted extensive studies for decades; however, FDD of supermarket refrigeration systems has not gained significant attention. Supermarkets consume around 50 kWh/ft 2 of electricity annually. The biggest consumer of energy in a supermarket is its refrigeration system, which accounts for 40%–60% of its total electricity usage and is equivalent to about 2%–3% of the total energy consumed by commercial buildings in the United States. Also, the supermarket refrigeration system is one of the biggest consumers of refrigerants. Reducing refrigerant usage or using environmentally friendly alternatives can result in significant climate benefits. A challenge is the lack of publicly available data sets to benchmark the system performance and record the faulted performance. This paper identifies common faults of supermarket refrigeration systems and conducts an experimental study to collect the faulted performance data and analyze these faults. This work provides a foundation for future research on the development of FDD methods and field automated FDD implementation.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

BOPTEST: Initial FRP Test Case Development

To support an emulator model development of Building Optimization Testing (BOPTEST) framework, a team at the US Department of Energy’s Oak Ridge National Laboratory developed a medium-sized office building written in Modelica to serve as a reference test case. The reference test case was modeled based on an actual research platform that represents a typical medium-sized office building. This test case would encourage model-based design and testing of new controllers in which a developer first prototypes and debugs on a model before implementing in the real world. The developed preliminary model and control parameters will be further calibrated and tuned with actual measured data from experiments

42 ENGINEERING↗

Empirical Validation of Multi-Zone HVAC System Model: Evaluation of Existing Infiltration Models used in Building Energy Simulation

Infiltration can have a significant impact on building loads. Studies have shown that infiltration can account for 15-40% of annual space conditioning needs in commercial buildings (Emmerich et al. 2019; Younes et al. 2012). The driving force of infiltration is the pressure difference across the building envelope caused by wind, the stack effect (known as buoyancy effect), and the operation of ventilation equipment. Wind pressure is governed by wind direction, speed, building shape, and other structures around the building. The stack effect is a function of the building height and air density differences of ambient air (Han, 2015). The effect of wind is dominant in low-rise residential buildings, and the stack effect is dominant in highrise buildings (ASHRAE 2017). In building energy simulation programs (e.g., EnergyPlus), various empirical infiltration models (e.g., the effective leakage area model, the flow coefficient model) are available to simulate infiltration rates. To help users in selecting a proper infiltration model for modeling of the two-story Flexible Research Platform (FRP), the team evaluates the existing infiltration models in EnergyPlus based on field measurements from the FRP. The blower door and tracer gas decay tests were performed in the FRP. The blower door test result was used to estimate input parameters required in the infiltration models. The actual infiltration rates were estimated with the tracer gas decay test results.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Tracer gas test in Net-Zero Energy Residential Test Facility

The Net-Zero Energy Residential Test Facility (NZERTF) at NIST was built in 2012 to support the development and adoption of cost-effective net-zero energy designs, technologies, and construction methods. It is two-story, and has four bedrooms, three bathrooms, and an open living room, dining room, and kitchen space. The NZERTF also has a basement and attic, both located within the conditioned space because the thermal and air-moisture barriers encompass the basement walls and attic roof. Transfer grilles link the living spaces to these two zones. The central heating and cooling system includes an air-toair heat pump, which delivers air to the basement, first and second floors. The heat pump has a cooling capacity of 7.6 kW and a heating capacity of 7.8 kW. The indoor unit is in the basement and ductwork runs along the basement ceiling. A balanced heat recovery ventilator (HRV) is installed in the basement and has its own dedicated ductwork. The HRV supplies 47 L/s of outdoor air to the house, with supplies on the first floor (in the kitchen/dining area) and in each of the three second-floor bedrooms. Air from the first-floor bathroom and both second-floor bathrooms is returned to the HRV before being exhausted, though the HRV was turned off during the tests. The house also has a range hood exhaust and a clothes dryer exhaust, both of which were turned off for the tests. The temperature of the house was measured and the operation of the space conditioning system, including its recirculating air distribution fan, were controlled by a commercially available thermostat.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Sensor Impacts Evaluation and Verification: Expert Interview Responses

The sensor configuration/deployment method has critical impacts on energy efficient building control and thermal comfort. However, traditional sensor techniques for building operation and fault detection and diagnostics (FDD) are not necessarily optimal in terms of energy efficiency and thermal comfort, and their global effects are not thoroughly investigated. In an effort to address and overcome this limitation, a multilaboratory and multiyear project, “Sensor Impact Evaluation and Verification,” was proposed. Its purpose is to develop a framework to investigate the impacts of sensor deployment and configuration on building energy optimization, FDD, occupant thermal comfort, and potentially grid efficiency. The first project task was a literature review to establish a solid knowledge of and a background related to sensor technologies and placement. To accomplish this task, an extensive review of previous research literature was performed. A series of expert interviews were conducted to augment the findings of the literature review. This report summarizes the interview design and interview results and findings. The interview was designed and performed to (1) investigate the current status and limitations of sensor configuration, (2) identify the research gaps and expectations for potential improvements in sensor configuration and deployment, and (3) integrate expert (e.g., researcher, building operation practitioner) knowledge and experience to develop use-case scenarios.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

A methodology for generating reduced-order models for large-scale buildings using the Krylov subspace method

Developing a computationally efficient but accurate building energy simulation (BES) model is important for many purposes. Model order reduction (MOR) methods are attractive and much more reliable than identification approaches, since it directly extract a lower-dimensional model from a detailed physics-based model without any pre-simulations. However, because of computational and data storage requirements, there are challenges of applying these methods to a large-scale building. To overcome the problem, this work introduces the Krylov subspace method to the building science field. Technical issues of applying the method to building applications are addressed and a suitable algorithm that overcomes those challenges is presented. Furthermore, to demonstrate the reliability of the algorithm, comparisons between the resulted reduced-order model (ROM) and a high-fidelity model from a commercial BES software for a 60-zone case study building are provided. The ROM was a factor of 100 faster than the high fidelity model but with high accuracy.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗

Literature Review for Sensor Impact Evaluation and Verification Use Cases - Building Controls and Fault Detection and Diagnosis (FDD)

This report summarizes a comprehensive literature review for the selected sensor suites used in building controls and fault detection and diagnostics (FDD), which is a Q2 deliverable of the Sensor Impact Evaluation and Verification project. The project’s overarching goal is to develop a framework for investigating the impact of sensor deployment and configuration for building energy optimization, fault detection and diagnosis (FDD), occupants’ thermal comfort, and potential grid efficiency. While the first phase of the literature review performed in Q1 reviewed the current methods of various sensor selection and placements and their impact, this report focuses on high impactful potential use cases for the selected sensor suites in building control and FDD. The use cases identified in this literature review will be further investigated and be included in the final sensor impact evaluation framework. For the review, the multi-laboratory team reviewed 241 research papers, technical reports, and books to identify existing technologies, the potential impact on energy savings and thermal comfort, and future research opportunities for the selected use cases in building controls and FDD. Along with the literature review, the team conducted a series of interviews with experts in sensors and controls area to identify the state-of-art sensor technologies, and the most impactful use cases in controls and FDD areas. The interview results will also be incorporated with the findings from the literature review in the next quarter, and the final use cases to be evaluated will be selected.

47 OTHER INSTRUMENTATION↗

Review: Sensor Impact on Building Controls and Automatic Fault Detection and Diagnosis (AFDD)

This report summarizes a literature review as a Q1 deliverable of the “Sensor Impact Evaluation and Verification” project. This project’s overarching goal is to develop a framework for investigating the impact of sensor deployment and configuration for building energy optimization, fault detection and diagnosis (FDD), occupants’ thermal comfort, and potential grid efficiency.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI↗