Engineering Papers⌕ Search

Engineering topics

Ayyanar, Raja

Publications and source records attributed to Ayyanar, Raja.

At least 19 records

Performance Specifications for Grid-Forming Technologies

Standards and specifications for inverter-based resources (IBRs) focus primarily on grid-following (GFL) technologies at present. Therefore, these may generally not be appropriate for application in power systems to ensure acceptable operation with grid-forming (GFM) technologies. In some cases, the direct application of prevailing standards and specifications may not be appropriate for - or may even inadvertently limit the potential of - GFM resources. The Universal Interoperability for Grid- Forming Inverters (UNIFI) Consortium is a U.S. Department of Energy funded effort to advance GFM technology. The UNIFI team brings together academic, industrial, and national-lab researchers as well as industry stakeholders (utilities, system operators, vendors) to collaboratively pursue advances in a broad range of GFM technologies. This paper introduces a set of system- and unit-level specifications driven by consensus across the UNIFI project team. These are intended to seamlessly integrate GFM technologies at any scale into power-systems operation and control in a vendor-agnostic manner. A suite of illustrative simulation results that demonstrate the application of and adherence to the proposed specifications are included.

grid-forming inverter↗

Novel Quadratic High Gain Boost Converter With Adaptive Soft-Switching Scheme and Reduced Conduction Loss

In this article, an improved soft-switching quadratic boost converter is proposed. Instead of inserting an additional active clamp or auxiliary zero-voltage transition circuit at the switching node, the proposed topology connects the high-voltage switching node to the input diode node by replacing one of the input diodes with a low-rated switch. The proposed topology can attain soft-switching condition for all the switches and input diode turns- off under zero-current switching (ZCS). The operation of input-side switch not only aids zero-voltage switching (ZVS) turn- on for the main switch but also helps in reducing the conduction loss. Also, the input-side switch operates under ZCS turn- on and ZVS turn- off , making it a loss economical solution. An adaptive timing scheme for driving the input switch is proposed, which can ensure soft-switching condition under varying gain and load range. The detailed operational modes, analysis, and design considerations of the proposed topology are presented. A 250 W hardware prototype is built to validate the performance of the proposed converter operating at 100 kHz switching frequency. Results with adaptive soft-switching scheme shows that the converter is modulated to achieve its best efficiency condition under various system conditions. Furthermore, a peak efficiency of 96.1% at 155 W and efficiencies above 95.75% over a wide load range are achieved using all Si devices.

14 SOLAR ENERGY↗

Mitigation of fault related voltage swell on distribution feeders using DER-based advanced inverter controls

Unbalanced faults in distribution feeders can impact voltages on the non-faulted phases. This paper models a real-life feeder with a high penetration level of solar photovoltaic (PV) units in detail including the secondary circuits, and shows a large voltage swell in one of the non-faulted phases of the feeder during a single line to ground fault. The voltages seen during this swell are more than 1.2 p.u., which can have detrimental impacts on the connected equipment and can also lead to loss of connected generation. The reason for this voltage swell is found to be the equivalent impedance at the fault location resulting from the ratio of zero and positive sequence cable impedances. It is seen that the connected solar PV units with appropriate control are able to reduce the severity of the voltage swell, especially for higher penetration levels of solar PV considered, but not entirely eliminate it.

14 SOLAR ENERGY↗

An Integrated Transmission-Distribution Co-Simulation for a Distribution System with High Renewable Penetration

Traditionally, transmission and distribution system dynamic simulations are performed independently. However, dynamic co-simulation of transmission-distribution systems can be beneficial in analyzing distribution systems with high penetration of distributed renewable resources. The authors describe a framework for conducting transmission-distribution dynamic co-simulation (TDDS). A model of a real network including detailed models of solar photovoltaic units in the distribution system is constructed. The initial operating point of the network is validated against field measurements. The TDDS tool is used to simulate a single line-to-ground fault on the distribution system, highlighting the need for conducting transmission-distribution co-simulations.

14 SOLAR ENERGY↗

Challenges and Solutions for Real-Time Phasor Modeling of Large-scale Distribution Network with High PV Penetration

The conversion process of a practical large-scale feeder data from a quasi-static time series (OpenDSS) model into a real-time phasor model (ePHASORSIM in Opal-RT) is discussed in the paper. The process is implemented using an open source Python software. Previous reported implementations for the conversion process lead to several errors when applied to a larger-scale system such as the one considered here. Hence in this work, we describe the common issues in this conversion and propose a customized solution to enhance the efficiency of the conversion and reduce the complexity in the process. A quantitative validation of the enhanced conversion process is presented in this work using an actual high PV penetration feeder model that consists of 2230 buses, and using actual load and PV profile data. After a detailed analysis, this customized conversion software will be made available as an open source tool and is expected to be helpful for researchers who want to pursue a similar conversion. Solutions to various observed issues such as identifying the lines due to islanded network, representation of full impedance model of transformer/lines as sequential models, complexity in the representation of single phase buses/lines as three phase buses/lines to make it compatible with the simulator platform are discussed. Comparison of power flow and time series simulation results obtained from both OpenDSS and ePHASORsim models show very low errors, validating the accuracy of the proposed conversion process.

14 SOLAR ENERGY↗

GaN‐based split phase transformer‐less PV inverter with auxiliary ZVT circuit

This paper explores performance enhancement of the common ground dynamic dc‐link (CGDL) inverter for single phase photovoltaic (PV) applications by a combination of gallium nitride (GaN) devices, split phase topology, coupled inductors, and zero voltage transition (ZVT) scheme. The CGDL inverter has the inherent advantage of minimised dc‐link capacitance and negligible leakage current due to the common ground configuration, but its reported efficiency was usually lower because of the higher dc‐link voltage used for the reduction of decoupling capacitance to a great extent. To solve the efficiency problem, in this study, a soft switching circuit is proposed for the first stage, while a coupled inductor integrated magnetics is incorporated in the second stage to reduce inductor loss, volume, and cost. Both of these topological improvements combined with the use of GaN devices facilitate in achieving high efficiency without compromising converter power density. Extensive experimental results are provided from a GaN based 1 kVA hardware prototype to demonstrate the superior performance of the CGDL inverter attaining a peak efficiency of 98.7% and a California Energy Commission efficiency of 98.5% at 75/50 kHz switching frequency.

Xia, Yinglai↗

Design and Scheduling of Microgrids using Benders Decomposition

The distribution feeder laterals in a distribution feeder with relatively high PV generation as compared to the load can be operated as microgrids to achieve reliability, power quality and economic benefits. However, renewable resources are intermittent and stochastic in nature. A novel approach for sizing and scheduling an energy storage system and microturbine for reliable operation of microgrids is proposed. The size and schedule of an energy storage system and microturbine are determined using Benders' decomposition, considering PV generation as a stochastic resource.

24 POWER TRANSMISSION AND DISTRIBUTION↗

Methods for Dynamic Analysis of Distribution Feeders with High Penetration of PV Generators

An increase in the number of inverter-interfaced photovoltaic (PV) generators on existing distribution feeders affects the design, operation, and control of the distribution systems. Existing distribution system analysis tools are capable of supporting only snapshot and quasi-static analyses. Capturing the dynamic effects of PV generators during the variation in distribution system states is necessary when studying the effects of controller bandwidths, multiple voltage correction devices, and anti-islanding. This work explores the use of dynamic phasors and differential algebraic equations (DAE) for impact analysis of PV generators on the existing distribution feeders.

14 SOLAR ENERGY↗

Accelerated testing of module-level power electronics for long-term reliability

This work has applied a suite of long-term-reliability accelerated tests to a variety of module-level power electronics (MLPE) devices (such as microinverters and optimizers) from five different manufacturers. This dataset is one of the first (only the paper by Parker et al. entitled “Dominant factors affecting reliability of alternating current photovoltaic modules,” in Proc. 42nd IEEE Photovoltaic Spec. Conf., 2015, is reported for reliability testing in the literature), as well as the largest, experimental sets in public literature, both in the sample size (five manufacturers including both dc/dc and dc/ac units and 20 units for each test) and the number of experiments (six different experimental test conditions) for MLPE devices. The accelerated stress tests (thermal cycling test per IEC 61215 profile, damp heat test per IEC 61215 profile, and static temperature tests at 100 and 125 °C) were performed under powered and unpowered conditions. The first independent long-term experimental data regarding damp heat and grid transient testing, as well as the longest term (>9 month) testing of MLPE units reported in the literature for thermal cycling and high-temperature operating life, are included in these experiments. Additionally, this work is the first to show in situ power measurements, as well as periodic efficiency measurements over a series of experimental tests, demonstrating whether certain tests result in long-term degradation or immediate catastrophic failures. Lastly, the result of this testing highlights the performance of MLPE units under the application of several accelerated environmental stressors.

14 SOLAR ENERGY↗