Holistic energy analysis method for thermal management architectures of data centers

Modern high-performance computing (HPC) data centers (DCs), particularly those supporting energy-intensive artificial intelligence (AI) workloads, face escalating thermal management challenges that degrade performance through thermal throttling and drive up cooling power consumption and operational costs. To address this challenge, many have developed a wide variety of thermal management solutions (single-phase, two-phase, direct, indirect, hybrid, and more) which attempt to cool HPC DCs effectively while attempting to minimize overall system power consumption. However, the analysis of these solutions and methods to effectively compare one with another is lacking. Overall power usage effectiveness (PUE) and total-power usage effectiveness (TUE) provide a metric to quantify power consumption but fail to identify components in the system which require further optimization. To address this, we propose a holistic analytical framework – the waterfall diagram (WFD) – which leverages a waterfall chart methodology, offering a comprehensive visualization of both the thermal management system loop and heat flow pathways from individual server components to the outdoor ambient. Use of the WFD enables graphical estimations of power efficiency and cooling performance across each component of a DC cooling system and complements Sankey-style energy flow visualizations by additionally resolving stage-wise temperature changes and incremental TUE contributions. The framework is used in conjunction with simulation-based approaches, to conduct a detailed pressure drop and flow distribution analysis aimed at identifying the optimal coolant distribution architecture for a single-phase direct-to-chip water-cooled DC, which serves as the baseline for subsequent WFD analysis. Among the evaluated architectures, the 3 U modular coolant distribution architecture is found to demonstrate the best performance, considering minimal pressure drop and uniform flow distribution. In addition, TUE is calculated for each cooling loop component based on its associated pressure drop and corresponding pumping power, which are integrated into the WFD. This correlation between TUE and local temperature offers immediate insight into the power efficiency and thermal performance contributions of individual components, facilitating further development and optimization. Examples of WFD applications are presented under varying thermal loads and ambient conditions, demonstrating reasonable cooling strategies. Notably, the 3 U modular architecture maintains a consistent chip case temperature of 85°C, achieving a TUE of 1.016 at ambient temperature of 47°C, and a TUE of 1.026 at ambient temperature of 52°C. The WFD methodology provides an efficient, holistic, and streamlined framework for DC thermal management architecture assessment and enables design optimization which is important for addressing the thermal-fluidic energy challenges of current and next-generation DCs.

32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATI